C&I Energy Storage

AC booster all-in-one machine

Electrical Energy Storage Industry Solutions

AC booster all-in-one machine
  • Model: DA-C5
  • Size: 5500×2800×3000mm
  • Color: Grey
  • Weight:

Excellent grid adaptability, fast acceptance of grid dispatching, and realization of grid dispatching

Pcs uses superior control algorithms to achieve lower harmonic outputs, smaller DC components, and more perfect grid-connected waveform outputs

The booster transformer adopts a bucket-type cooling design, which improves the heat dissipation efficiency by 30% and the operation stability of the transformer by 40%.

Integrated cabin design reduces the need for floor space for equipment layout and reduces transportation, installation and maintenance costs

Specifications

DC Side Parameters
Max input voltage1500V
Battery pack voltage range1050~1500V
Max DC current2551A / 2551A*2
Number of connectable battery packs1
AC Side Parameters (Grid-tied)
Rated AC power2500kVA@45℃ / 5000kVA@45℃
Max AC power2750kVA@30℃ / 5500kVA@30℃
Rated AC current2551A / 2551A*2
Rated AC voltage690V
AC voltage range587~759V
Rated grid frequency50Hz / 45~55Hz
THDi<3% (rated power)
Power factor>0.99 (rated power)
Reactive power adjustable range-100%~100%
Input phase / Output phase3/3
AC Side Parameters (Off-grid)
Rated AC voltage690V
AC voltage range587~759V
THDu<3% (linear load)
DC voltage component<0.5% Un (linear balanced load)
Unbalanced load capacity100% (linear load)
Rated grid frequency50Hz / 45~55Hz
Efficiency
Maximum converter efficiency99%
Transformer Parameters
Transformer rated power2500kVA / 5000kVA
Transformer max power2750kVA / 5500kVA
LV / MV voltage: 0.69kV / 10kV0.69kV / 35kV
Transformer connection groupDy11
Protection
DC input protectionCircuit breaker + Fuse
AC output protectionCircuit breaker
Surge protectionDC Type II / AC Type II
Grid monitoring / Leakage current detectionAvailable / Available
Insulation detectionAvailable
Overheat protectionAvailable
Other Parameters
Display & operationTouch screen
Protection classIP65(Converter) IP54(Others)
Operating temperature range-30~+60℃(Derating above 45℃)
Allowable humidity range0~95%(non-condensing)
AltitudeMax 3000m (Derating above 2000m)
Cooling methodForced air cooling
Communication protocolModbus-RTU, Ethernet, CAN2.0B, Modbus-TCP
Pre-control typeCabinet type
Overall dimensions(W*D*H)5500×2800×3000mm / 6800×3200×3100mm